• HeySun® SHS Outdoor Series — Three-Phase Hybrid Solar Inverter 4–50 kW
HeySun® SHS Outdoor Series — Three-Phase Hybrid Solar Inverter 4–50 kW
+

Share

HeySun® SHS Outdoor Series — Three-Phase Hybrid Solar Inverter 4–50 kW

HeySun SHS Outdoor three-phase hybrid inverter, 4–50 kW, 380 V, IP65. 1000 V PV input, 137–750 V lithium battery, for three-phase loads.

Consult now


Category:

Residential PV System

Keywords:

  • Product Description
  • HeySun® SHS Outdoor Series — Three-Phase Hybrid Solar Inverter 4–50 kW

    Series 03 of 03 — Outdoor IP65, three-phase 380 V, high-voltage lithium platform

    Model codes: HPY-SHS-4K-on through HPY-SHS-50K-on

    Choose the three-phase series when the load itself is three-phase — pumps, lifts, workshop machinery, cold rooms — or when the site is simply larger than a single-phase supply can carry. 1000 V PV input keeps strings long and combiners few, while the IP65 outdoor cabinet avoids a dedicated electrical room.


    System Diagram

    Product Overview

    The HeySun® SHS Outdoor Three-Phase Series is the highest-capacity member of the SHS hybrid family, scaling the platform from 4 kW to 50 kW on a 3L/N/PE 380 V supply. Unlike the single-phase series, it is built for premises where three-phase machinery, pumps, lifts or workshop tools must not stop; unlike the indoor series, it lives outdoors and works on a high-voltage lithium battery.

    Typical duties include large residential compounds with three-phase distribution, guesthouses and small hotels, workshops, cold stores, water pumping and agricultural processing. Because the platform is parallel-ready, capacity can be added over time instead of being oversized at day one.

    Key Features

    ⚡ 4–50 kW Three-Phase Output — 3L/N/PE, 380 V, 50 / 60 Hz for three-phase premises and machinery.
    🌧️ IP65 Outdoor Cabinet — Weatherproof enclosure for direct outdoor installation.
    📶 1000 V PV Input — Long strings and fewer combiners for large roof or ground arrays.
    🔋 High-Voltage Lithium Platform — 137–750 V battery bus with bidirectional energy flow.
    👥 Parallel-Ready — Parallel operation supported for staged capacity growth.
    🔄 Grid-Tied, Off-Grid & Hybrid — Configurable operating modes for self-consumption, backup or island operation.
    📱 App Monitoring — Remote status, fault diagnosis and energy reporting.
    🛡️ Industrial Protection Package — Comprehensive electrical and thermal protection for continuous duty.

    Technical Specifications

    ItemSpecification
    Model code rangeHPY-SHS-4K-on … HPY-SHS-50K-on
    Power range4–50 kW
    Grid / off-grid voltage3L/N/PE, 380 V, 50 / 60 Hz
    Max. PV voltage1000 V
    Battery voltage137–750 V, lithium (LFP)
    Energy flowBidirectional energy storage
    Parallel operationSupported
    Work modesGrid-tied / off-grid / hybrid, user-configurable
    Ingress protectionIP65, suitable for outdoor installation

    Model selection follows the required power step, array size and battery capacity — contact us to configure the right unit. Detailed datasheets are available on request.

    Battery Sizing Guide

    Platform requirements: high-voltage lithium (LFP) bank on a 137–750 V bus, paralleled in steps as the site grows. The high bus voltage keeps DC current low (about 130 A at 50 kW), so the battery is normally sized by energy demand rather than by discharge rate.

    Three-step sizing:

    1. Night-time / backup energy = the load profile to be covered after sunset or through an outage. For commercial sites this is often taken from a measured load log rather than a rule of thumb.
    2. Required capacity = that energy ÷ depth of discharge (0.9 for LFP) ÷ system efficiency (about 0.9).
    3. Check the discharge rate and the expansion plan = peak three-phase load ÷ (capacity ÷ battery voltage); the platform is parallel-ready, so capacity can be added later instead of oversized at day one.

    Typical configuration — self-consumption with backup:

    Model groupTypical LFP capacityTypical duty
    HPY-SHS-4K-on … 10K-on10–20 kWhLarger residence or small guesthouse compound
    HPY-SHS-12K-on … 20K-on20–40 kWhGuesthouse, workshop, pumping with backup
    HPY-SHS-25K-on … 50K-on40–100 kWhCommercial or multi-building site, staged expansion

    Figures are typical reference values for self-consumption sizing, not a supply commitment; final sizing follows the load calculation for the specific site, and the selected battery must be compatible with the 137–750 V DC bus.

    PV Array Sizing Guide

    Inverter limits: maximum PV voltage 1 000 V across the series — long strings, fewer combiners and thinner DC cabling than a 500 V platform. The per-model maximum PV input power and MPPT configuration are given in the detailed datasheets (available on request); the array is sized with the design rules below and confirmed against the datasheet at order stage.

    Three-step sizing:

    1. Required array power = daily energy demand ÷ (peak sun hours × performance ratio). Take the performance ratio as 0.75–0.8 and the peak sun hours from local solar data; for commercial sites the daily demand usually comes from a measured load log.
    2. DC/AC ratio = array kWp ÷ inverter rated output. A ratio of about 1.1–1.3 is typical: it maximises harvest across the day while keeping clipping losses low.
    3. String design — modules in series must keep the open-circuit voltage (calculated at the coldest site temperature) below 1 000 V; strings are then distributed across the MPPT trackers according to the datasheet limits, with roof or ground fields balanced per tracker.

    Typical array (DC/AC 1.1–1.3, 630 Wp mono-crystalline modules):

    Model groupTypical arrayTypical duty
    HPY-SHS-4K-on … 10K-on4.5–13 kWpLarge residence, guesthouse compound
    HPY-SHS-12K-on … 20K-on13–26 kWpWorkshop, cold store, pumping station
    HPY-SHS-25K-on … 50K-on28–65 kWpCommercial or multi-building site

    String counts per tracker, cable sizing and protection layout are confirmed in the project design; the array should also match the battery recharge requirement calculated in the guide above. Figures are typical reference values, not a supply commitment.

    Typical Applications

    🏢 Large residential compounds — three-phase distribution with battery backup.
    🏨 Guesthouses & small hotels — cut diesel consumption and ride through outages.
    🔧 Workshops & light industry — keep three-phase machinery running.
    💧 Pumping & agriculture — daytime solar pumping with battery buffer.
    ❄️ Cold storage — protect temperature-critical loads from grid failure.

    Other Series in the SHS Range

    SHS Indoor, 3.3–12.3 kW — indoor high-frequency unit on a 24 / 48 V battery platform, for homes with a technical room.
    SHS Outdoor Single-Phase, 3–8 kW — IP65 single-phase unit for homes without a technical room.


    Web: www.bjhpy.com  |  E-mail: info@bjhpy.com

Consult now